100Kva silent generator sets with Cummins engine, Sound and water proof enclosure
Basic Info
Model No.: 6BT5.9-G2
Product Description
100kva silent generator set, powered by Cummins 6BT5.9-G2 Engine
Stamford alterantor
Deepsea control panel
High quality
Every generator set is subjected to a comprehensivetest program which includes 50% load, 75% load,100% load, 110% load and the checking and proving of all control and safety shut-down functions;
24V DC start motor;
Equipped with battery charger and 24V highperformance maintenance-free lead-acid startingbatteries and connecting with cables;
Equipped with industrial silencer and flexible exhaust hose;
Equipped with CHINT MCCB circuit breaker;
Designed to Comply with ISO8528/GB2820;
Powered by Cummins engine,Controlled by Deepsea panel
Voltage | HZ | Phase | P.F (COS) | Output (KVA) |
400/230V | 50 | 3 | 0.8 | 100 |
Remark | 60Hz, 220, 380V, 460V, 480V, 600V can be produced as requirements. |
Cummins Diesel Generator power capacity
Engine Model | 6BT5.9-G2 |
Number of Cylinders | 6 cylinders in line |
Cycle | 4 stroke |
Aspiration | Turbocharged and after water cooled |
Bore×Stroke | 102mm x120mm |
Displacement | 5.9L |
Compression ratio | 17.5:1 |
Prime Power/Speed | 86KW / 1500rpm |
Standby Power/Speed | 92KW / 1500rpm |
Speed Governor | Electrical |
Cooling System | Forced water cooling cycle |
Steady speed droop | ≤1% |
Total lubrication system capacity | 16.4L |
Coolant capacity (engine only) | 9.1L |
Fuel Consumption at 100% Load | 208g/kw.h |
Starter Motor | DC24V, |
DC24V |
Alternator brand | Stamford, Marathon, Leroy Somer, Mecc-alte, TWGII… |
Prime power | 100Kva |
Frequency/speed | 50HZ/1500rpm (60Hz/1800rpm) |
Exciter type | Single bearing, Brushless, Self-excited |
Power factor | 0.8 |
Voltage adjust range | ≥5% |
Voltage regulation NL-FL | ≤±1% |
Insulation Grade | H |
Protection Grade | IP23 |
Control Panel
The control module gives digital readouts of:
Generator voltage;
Output frequency;
Engine speed;
Battery voltage;
Engine hours run.
The control module has indicators for failure
information:
Overspeed/underspeed,
Emergency stop
Low oil pressure;
High water temperature
Failure to start
Battery charger failure
Automatic shutdown occurs under:
Low engine oil pressure;
High engine water temperature;
Overspeed/underspeed;
Failure to start after three attempts.