Find Power Group-Generator, Engine, Diesel Generator on Industry Directory, Reliable Manufacturer/Supplier/Factory from China.

Inquiry Basket (0)
Home > Products > Sutech Power Group-Generator > Powered By Shangchai Engine > Cheap price 320kw super silent generator with Shangchai SC15G500D2 new engine

Cheap price 320kw super silent generator with Shangchai SC15G500D2 new engine

Basic Info

Model No.: SC15G500D2

Product Description

320kw silent Shangchai diesel generators

New enginSC15G500D2

Main technical data

Shangchai Engine

Every generator set is subjected to a comprehensivetest program which includes 50% load, 75% load,100% load, 110% load and the checking and proving of all control and safety shut-down functions;

24V DC start motor;

Equipped with battery charger and 24V highperformance maintenance-free lead-acid startingbatteries and connecting with cables;

Equipped with industrial silencer and flexible exhaust hose;

Equipped with CHINT MCCB circuit breaker;

Designed to Comply with ISO8528/GB2820;

Powered by Shangchai engine,Controlled by Deepsea panel

 

Voltage

HZ

Phase

P.F

(COS)

Output

(KVA)

400/230V

50

3

0.8

400

Remark

60Hz, 220, 380V, 460V, 480V, 600V can be produced as requirements.

Engine

Shangchai Diesel Generator power capacity

 

Shangchai new engine SC15G500D2 Engine Specification

Engine Model

SC15G500D2

Number of Cylinders

6 cylinders, Vertical in line

Cycle

4 stroke

Aspiration

Turbocharged and after water cooled

Bore×Stroke

135mm x165mm

Displacement

14.16L

Compression ratio

15.5:1

PrimePower/Speed

327 KW / 1500rpm

Standby Power/Speed

363KW / 1500rpm

Speed Governor

electrical

Cooling System

Forced water cooling cycle

Steady speed droop

1%

Total lubrication system capacity

37L

Coolant capacity (engine only)

20L

Fuel Consumption at 100% Load

70L

Starter Motor

DC24V,

Alternator

DC24V

 

 

Model Prime power Engine model No.of cyls Bore/stroke (mm) Fuel Cons. (g/kwh) Dimension   (L*W*H) (mm) Weight(kg)
KW KVA
ST-S50GF 50 62.5 SC4H95D2 4 105*124 205 2200*800*1380 1000
ST-S75GF 75 93.75 SC4H115D2 4 105*124 205 2200*900*1380 1100
ST-S100GF 100 125  SC4H160D2  4 105*124 205 2500*900*1500 1200
ST-S100GF 100 125 6135AD-3 6 135*150 226 2600*900*1600 2100
ST-S120GF 120 150 SC4H180D2 4 105*124 205 2700*900*1650 1300
ST-S150GF 150 187.5  SC7H230D2 6 105*124 195 2700*900*1650 1500
ST-S150GF 150 187.5 6135AZD-1 6 135*150 226 2700*900*1650 2200
ST-S170GF 170 212.5  SC7H250D2 6 105*124 198 2800*900*1700 1900
ST-S180GF 180 225  SC9D280D2 6 114*144 198 2800*900*1700 2100
ST-S200GF 200 250 6135AZLD 6 135*150 225 2900*1200*1800 2650
ST-S200GF 200 250 G128ZLD2 6 135*150 225 2900*1200*1800 2650
ST-S250GF 250 312.5 G128ZLD1 6 135*150 225 3000*1300*1800 2800
ST-S280GF 280 350 G128ZLD11 6 135*150 225 3000*1300*1800 2800
ST-S300GF 300 375 SC12E460D2 6 128*153 198 3000*1300*1950 2700
ST-S300GF 300 375 12V135AZD  12 135*150 225 3200*1350*1950 3450
ST-S320GF 320 400 SC15G500D2 6 135*165 200 3000*1250*1950 2900
ST-S350GF 350 437.5 12V135AZLD  12 135*150 225 3300*1350*1950 3800
ST-S400GF 400 500 12V135BZLD  12 135*150 225 3400*1500*1950 4200
ST-S450GF 450 562.5 12V135BZLD2 12 135*150 225 3500*1500*1950 4500
ST-S500GF 500 625 12V135BZLD1 12 135*150 225 3500*1500*1950 4800
ST-S550GF 550 687.5 SC27G830D2 12 135*155 210 3600*1600*1950 5000
ST-S600GF 600 750 SC33W990D2 6 180*215 215 3700*1700*1950 5300
ST-S660GF 660 825 SC33W990D2 6 180*215 215 3750*1700*1950 5500
Alternator

 

Alternator brand

Stamford, Marathon, Leroy Somer, Mecc-alte, TWGII…

Prime power

400kva

Frequency/speed

50HZ/1500rpm (60Hz/1800rpm)

Exciter type

Single bearing, Brushless, Self-excited

Power factor

0.8

Voltage adjust range

5%

Voltage regulation NL-FL

≤±1%

Insulation Grade

H

Protection Grade

IP23

Control panel

 The control module gives digital readouts of:

Generator voltage;

Output frequency;

Engine speed;

Battery voltage;

Engine hours run.

The control module has indicators for failure

information:

Overspeed/underspeed,

Emergency stop

Low oil pressure;

High water temperature

Failure to start

Battery charger failure

Automatic shutdown occurs under:

Low engine oil pressure;

High engine water temperature;

Overspeed/underspeed;

Failure to start after three attempts.

Pictures FYI

 

 

 

 

Contact us

Sutech Power Co., Ltd

No.18 Hailing Industry Park, Taizhou City, Jiangsu Province, China

Mobile: +86-15161006661

Tel: +86-523-86282985

Skype: stmeco

Product Categories : Sutech Power Group-Generator > Powered By Shangchai Engine